Introduction

CEPT, A Living Laboratory

Energy Efficient Design Features

Summary

Location Ahmedabad
Geographical coordinates 23° N, 73° E
Occupancy Type Office & Educational
Typology New Construction
Climate Type Hot and Dry
Project Area 498 m2
Grid Connectivity Grid connected
EPI 58 kWh/m2/yr

Passive Strategies

CEPT, A Living Laboratory

Passive Design Strategies

Orientation

The building is north-south oriented with appropriate shading and light shelves on the south.

Daylighting

Vision, clerestories, light shelves on south bring in diffuse daylight with occupant control. north light is used for introducing daylight into the building.

Active Strategies

CEPT, A Living Laboratory

Active Strategies

HVAC Technologies

  1. Mixed mode ventilation.
  2. Radiant cooling floor and ceiling panels for simulation lab and basement floor.
  3. VRF for dedicated outdoor air system at 3.51 COP with CO2 control.
  4. Air cooled chiller with 3.35 COP (ARI).
  5. Passive cooling in non-summer months with underground tank and evaporative fluid cooler.
  6. Premium efficiency pump motors with VFDs.

Lighting Design 

  1. Daylight autonomy 75% time for over 90% of spaces.
  2. Daylighting and vacancy sensor control of lights at 4.7 W/m2.
  3. Office equipment control with occupancy sensor control.

Renewable Energy

CEPT, A Living Laboratory

Renewable Energy

50%  roof covered with 27 kW PV panels tilted at 23º facing south for on-site generation equivalent to 70kWh/m2/yr.

More Information

CEPT, A Living Laboratory

http://www.carbse.org/a-living-laboratory/

Disclaimer: Reference in this Web site to any specific commercial products, processes, or services, or the use of any trade, firm or corporation name is for the information and convenience of the site’s visitor’s, and does not constitute endorsement, recommendation, or favoring by the Ministry of Power, Government of India, or Bureau of Energy Efficiency, Ministry of Power, Government of India. Additionally, the views and opinions of authors expressed herein do not necessarily state or reflect those of the Ministry of Power, Government of India, or Bureau of Energy Efficiency, Ministry of Power, Government of India, and shall not be used for advertising or product endorsement purposes.